CHEMVEN

Jar Test: Optimising Coagulant Dose Like a Water Engineer

To perform a proper jar test with turbidity measurement to optimise coagulant dose and pH.

Level: UniversitySafety: SafeTime: 60 min
Aim of Experiment: To perform a proper jar test with turbidity measurement to optimise coagulant dose and pH.

Theoretical Foundations

The jar test simulates waterworks coagulation: rapid mix disperses coagulant, slow mix grows flocs, settling separates them. Residual turbidity vs dose gives the optimum - applied colloid chemistry.

Required Apparatus & Chemicals

Laboratory Apparatus

  • Jar-test beakers (6)
  • Multiple stirrer or glass rods
  • Turbidimeter or visual tubes
  • pH paper/meter

Chemical Reagents

  • Turbid clay water
  • Alum solution (standardised)
  • Sodium hydroxide / HCl (pH adjustment)
  • Distilled water

Step-by-Step Practical Procedure

  1. Adjust six jars to pH 5.5-7.5 range (optional pH study).
  2. Dose 10-100 mg/L alum across jars.
  3. Rapid mix 1 min, slow mix 15 min, settle 20 min.
  4. Measure residual turbidity of each supernatant.
  5. Plot turbidity vs dose; find the minimum.
  6. Note floc size and settling speed.

Observations & Expected Results

Turbidity falls to a minimum at the optimum dose then rises slightly with overdose; best pH ~6-7 for alum.

Worked Stoichiometric Calculations

Problem: Residual turbidities (NTU) at 20, 40, 60, 80 mg/L alum: 45, 12, 4, 9. What is the optimum dose?

Working: 60 mg/L gives the lowest residual turbidity (4 NTU) - the optimum; 80 mg/L shows restabilisation.

Safety Precautions & Hazard Control

  • Identical mixing for all jars.
  • Sample supernatant without disturbing sediment.
  • Calibrate the turbidity comparison.

Waste Disposal Protocol

Sludge to bin; water to drain.

Viva Voce Oral Defense Questions & Answers

Q: Why is pH important for alum?

A: Al(OH)3 precipitates best near pH 6-7; too acidic keeps Al^3+ soluble, too alkaline gives aluminate.

Q: What is restabilisation?

A: Overdosed coagulant recharges particles, redispersing the colloid.

Q: How do engineers use this test?

A: To set daily coagulant doses as raw-water quality changes.

← Back to Experiments Directory